711.2.3 Supporting construction.
BC § 711.2.3
The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported. Exception: In buildings of Type IIB, IIIB or VB construction, the construction supporting the horizontal assembly is not required to be fire-resistance-rated at the following: 1. Horizontal assemblies at the separations of incidental uses as specified by Table 509 provided the required fire-resistance rating does not exceed 1 hour.
2.Horizontal assemblies at the separations of dwelling units and sleeping units as required by Section 420.3.
3.Horizontal assemblies at smoke barriers constructed in accordance with Section 709.