314.2.2 Drain pipe materials and sizes.
PC § 314.2.2
Components of the condensate disposal system shall be cast iron, galvanized steel, copper, cross-linked polyethylene, polyethylene, ABS, CPVC, or PVC pipe or tubing. Polypropylene tubing may be used in lengths that do not exceed 12 inches (304.8 mm) for an individual drain application. Components shall be selected for the pressure and temperature rating of the installation. Joints and connections shall be made in accordance with the applicable provisions of Chapter 7 relative to the material type. Condensate waste and drain line size shall be not less than 3/4-inch (19.1 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal. Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with Table 314.2.2. Table 314.2.2Condensate Drain Sizing Equipment CapacityMinimum Condensate Pipe DiameterUp to 20 tons of refrigeration3/4 inchOver 20 tons to 40 tons of refrigeration1 inchOver 40 tons to 90 tons of refrigeration1 1/4 inchesOver 90 tons to 125 tons of refrigeration1 1/2 inchesOver 125 tons to 250 tons of refrigeration2 inches For SI: 1 inch = 25.4 mm, 1 ton of capacity = 3.517 kW. (Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023) Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.