1106.3 Vertical leader sizing.

PC § 1106.3

Vertical leaders shall be sized based on the flow rate from horizontal gutters or the maximum flow rate through roof drains. The flow rate through vertical leaders shall not exceed that specified in Table 1106.3. Table 1106.3Vertical Leader Sizing Size of Leader(inches)Capacity(gpm)Size of Leader(inches)Capacity(gpm)2302 × 2301 1/2 × 2 1/2302 1/2542 1/2 × 2 1/2543922 × 4922 1/2 × 39241923 × 4 1/41923 1/2 × 419253604 × 53604 1/2 × 4 1/236065635 × 65635 1/2 × 5 1/2563812086 × 81208 For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1106.3?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters