1106.2 Size of storm drain piping.
PC § 1106.2
Vertical and horizontal storm drain piping shall be sized based on the flow rate through the roof drain. The flow rate in storm drain piping shall not exceed that specified in Table 1106.2. Table 1106.2Storm Drain Pipe Sizing Pipe Size(inches)Capacity (gpm)Vertical DrainSlope of Horizontal Drain1/16 inchper foot1/8 inchper foot1/4 inchper foot1/2 inchper footPipe Size(inches)Capacity (gpm)Vertical DrainSlope of Horizontal Drain1/16 inchper foot1/8 inchper foot1/4 inchper foot1/2 inchper foot234152231443873955791114180811151632315311117165234331653824334448768981,1175057141,0101,429102,0509271,3111,8552,623123,2721,4802,0932,9604,187144,2041,3121,8562,6213,713155,5432,5083,5465,0167,093165,5432,5083,5465,0167,093188.2183,1004,3866,1928,773