605.10.3 Prohibited use.
FC § 605.10.3
It shall be unlawful to use portable electric space heaters in the following locations: 1. In any building or occupancy, where the power requirements for the portable electric space heater exceed the rating of the electrical circuit or receptacle from which the heater will draw current.
2.In any occupancy, within 3 feet (914 mm) of any combustible material.
3.In Group I-2 occupancies, except that a portable electric space heater with a heating element designed not to exceed a temperature of 212°F (100°C) may be used in nonsleeping staff and employee areas.
4.In Group R-1 college and university dormitories.
5.In any location considered to be a hazardous location in accordance with the Electrical Code, unless listed for such use.