6004.3.2.1.1 Distance limitation to exposures.
FC § 6004.3.2.1.1
Outdoor storage, handling or use of highly toxic or toxic compressed gases shall not be located within 75 feet (22 860 mm) of a lot line, public street, private road, exit discharge or building not associated with the manufacture or distribution of such gases, unless all of the following conditions are met: 1. Storage is shielded by a 2-hour fire-resistant barrier which interrupts the line of sight between the storage and the exposure.
2.The 2-hour fire-resistant barrier shall be located at least 5 feet (1524 mm) from any exposure.