5707.4 Location of dispensing at fleet facility.
FC § 5707.4
Fleet fueling may be conducted at a designated location at the fleet facility and/or by proceeding from vehicle to vehicle, as approved by the department. Fleet fueling shall not be conducted at the following locations: 1. On public streets; 2. On fire apparatus access roads; 3. Inside buildings; 4. On the roof level of parking structures or other buildings; 5. Less than 10 feet (3048 mm) from buildings or property lines; 6. Less than 15 feet (4572 mm) from combustible material or waste; 7. Less than 25 feet (7620 mm) from any flammable gas storage area; and 8. Less than 25 feet (7620 mm) from any smoking, open flames or other source of ignition.
9.Less than 10 feet (3048 mm) from overhead powerlines or other aboveground electrical installation, measured from the boundary of the utility easement, or, if there is no easement, from the vertical plane of the installation at its widest point; or 10. Less than 10 feet (3048 mm) from the boundary of any transportation easement, including bridges and tunnels, as measured from the vertical plane of the easement at its widest point.