This section outlines the color-coding requirements for various fire protection systems, including standpipe, sprinkler, and extinguishing systems. It specifies the colors to be used for piping, valves, and connections, along with signage requirements for foam systems. Applies to building owners responsible for fire safety compliance.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

5706.4.10.8.1 Color coding.

FC § 5706.4.10.8.1

Fire protection systems shall be color-coded as follows: 1. Standpipe and/or yard hydrant systems: 1.1. Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting white bands. 1.2. Fire department connections: Red.

2.Sprinkler systems (wet or dry): 2.1. Piping and valve bodies and handles: Red with contrasting bright green bands. 2.2. Fire department connections: Red with green caps.

3.Nonautomatic sprinkler systems (including fog spray systems): 3.1. Piping and valve bodies and handles: Red with contrasting aluminum bands. 3.2. Fire department connections: Aluminum.

4.Carbon dioxide extinguishing systems – piping, valve bodies and handles: Red with contrasting brown bands.

5.Steam extinguishing systems – piping, valve bodies and handles: Red with contrasting black bands.

6.Foam extinguishing systems: 6.1. Piping, valve bodies and handles, hydrants and hydrant or hose houses: Red with contrasting bright orange bands. 6.2. Department water connections: Red. A durable sign that reads "WATER FOR FOAM SYSTEM", shall be conspicuously posted immediately adjacent to such connections. 6.3. Department foam connection: Red with contrasting bright orange band or caps. A durable sign that reads "CHEMICAL FOAM DIRECT TO TANKS" or "...% MECHANICAL FOAM SOLUTION DIRECT TO TANKS", shall be conspicuously posted immediately adjacent to such connections.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 5706.4.10.8.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters