5705.5.2 Wall-mounted dispenser installation.
FC § 5705.5.2
Except as otherwise provided in FC 5705.5.4, wall-mounted dispensers shall be installed in compliance with the following requirements: 1. The bottom of each wall-mounted dispenser shall be a minimum of 42 inches (1067 mm) and a maximum of 48 inches (1219 mm) above the finished floor.
2.The wall space between the dispenser and the floor shall remain clear and unobstructed.
3.The minimum separation between dispensers shall be 48 inches (1219 mm).
4.The maximum capacity of each dispenser installed in a public hallway shall be 41 fluid ounces (1.21 L).
5.The maximum quantity allowed in a public hallway within a control area shall be 10 gallons (38 L), unless the public hallway is protected throughout by a sprinkler system or a smoke detection system.
6.Projections into a public hallway shall be in accordance with the construction codes, including the Building Code.