5705.4.9 Portable fire extinguishers.
FC § 5705.4.9
Portable fire extinguishers shall be provided in accordance with FC 906. At least one portable fire extinguisher having a rating of not less than 40-B shall be located not less than 10 feet (3048 mm) or more than 30 feet (9144 mm) from any solvent distillation unit.