5705.3.8.2 Location.
FC § 5705.3.8.2
Dispensing activities which exceed the quantities set forth in FC Table 5705.3.8.2 shall not be conducted within 15 feet (4572 mm) of buildings or combustible materials or within 25 feet (7620 mm) of building openings, lot lines, public streets or private roads. Dispensing activities that exceed the quantities set forth in FC Table 5705.3.8.2 shall not be conducted within 15 feet (4572 mm) of storage of Class I, II or III liquids unless such liquids are stored in tanks which are listed and labeled as 2-hour protected tank assemblies in accordance with UL 2085. The commissioner may impose by rule, or as a condition of a permit, additional restrictions on dispensing activities, including dispensing locations, dispenser requirements, container requirements and fire protection requirements, upon a determination that such additional restrictions are required in the interest of public safety. Exceptions: 1. The requirements shall not apply to areas where only the following liquids are dispensed: Class III liquids; liquids that are heavier than water; water-miscible liquids; and liquids with viscosities greater than 10,000 centipoise (cp).
2.Flammable and combustible liquid dispensing in chemical plants, process facilities, oil blending and packaging facilities, bulk plants and terminals. FC Table 5705.3.8.2Maximum Allowable Quantities for Dispensing of Flammable and Combustible Liquids in Outdoor Control Areas a Class of LiquidQuantity (gallons)Flammable Class IA Class IB Class IC Combination Class IA, IB and IC10152030 cCombustible Class II Class IIIA Class IIIB30803,300 For SI: 1 gallon = 3.785 L. a. For definition of "Outdoor Control Area", see FC 202. b. Reserved. c. Containing not more than the maximum allowable quantity per control area of each individual class.