5705.3.5.3 Quantities exceeding limits for control areas.
FC § 5705.3.5.3
Quantities exceeding the maximum allowable quantity per control area indicated in FC 5705.3.5.1 and 5705.3.5.2 shall be in compliance with the following requirements: 1. For open systems, indoor use of flammable and combustible liquids, including the dispensing and mixing of such liquids, shall be within a room or building complying with the construction codes, including the Building Code and FC 5705.3.7.1 through 5705.3.7.5.
2.For closed systems, indoor use of flammable and combustible liquids, including the dispensing and mixing of such liquids, shall be within a room or building complying with the requirements of the construction codes, including the Building Code and FC 5705.3.7 through 5705.3.7.4 and 5705.3.7.6.