5705.3.5.1 Maximum allowable quantity per control area.
FC § 5705.3.5.1
Indoor use of flammable and combustible liquids, including the dispensing and mixing of such liquids, shall not exceed the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) and shall not exceed the additional limitations set forth in FC 5705.3.5. Exceptions: 1. Cleaning with Class I, II and IIIA liquids shall be in accordance with FC 5705.3.6.
2.Use of hazardous production material flammable and combustible liquids in Group H-5 occupancies shall be in accordance with FC Chapter 27.