5704.4.2.4 Storage adjacent to buildings.
FC § 5704.4.2.4
A maximum amount of 1,100 gallons (4163 L) of flammable and combustible liquids stored in portable containers may be stored adjacent to a building located on the same premises and under the same ownership, provided that: 1. The building does not exceed one story in height. Such building shall be of fire-resistance-rated construction with noncombustible exterior surfaces or noncombustible construction and shall be used principally for the storage of liquids; or 2. The exterior building wall adjacent to the storage area shall have a fire-resistance rating of not less than 2 hours, having no openings to above grade areas within 10 feet (3048 mm) horizontally of such storage and no openings to below grade areas within 50 feet (15 240 mm) horizontally of such storage.