What is NYC FC § 5704.2.11.4?

Quick Answer

This section mandates that fill pipes be equipped with a spill container of at least 15 gallons and an approved overfill prevention system to prevent overflow. Compliance with NFPA 30 and FC 5704.2.9.4 is required. Applies to building owners managing fuel storage systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

5704.2.11.4 Overfill protection and prevention systems.

FC § 5704.2.11.4

Fill pipes shall be equipped with a spill container of not less than 15-gallon (56.8 L) capacity and an approved overfill prevention system to automatically prevent overflow in accordance with NFPA 30 and FC 5704.2.9.4.