5604.5.1.2 Construction.
FC § 5604.5.1.2
Indoor magazines shall be designed and installed in compliance with the following requirements: 1. The magazine shall be fire resistant and theft resistant.
2.The exterior of the magazine shall be painted red.
3.The base of the magazine shall be fitted with wheels, casters or rollers to facilitate removal from the building in an emergency.
4.The lid or door of the magazine shall be marked with conspicuous white lettering not less than 3 inches (76 mm) high and minimum 1/2-inch (12.7-mm) stroke, reading "EXPLOSIVES – KEEP FIRE AWAY – NO SMOKING".
5.The least horizontal dimension of the magazine shall not exceed the clear width of the entrance door.