This section outlines the requirements for sizing pressure relief devices associated with cryogenic containers. The devices must be capable of preventing the maximum allowable working pressure (MAWP) from being exceeded and must be clearly marked by the manufacturer with their set pressure. Applies to operators of cryogenic systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

5503.2.3 Sizing.

FC § 5503.2.3

Pressure relief devices shall be sized in accordance with the specifications to which the cryogenic container was fabricated. The relief devices shall have sufficient capacity to prevent the MAWP of the cryogenic container or system from being exceeded. It shall be unlawful to use pressure relief devices that are not clearly marked by the manufacturer with their set pressure.