5106.5.8 Flammable and combustible liquids.
FC § 5106.5.8
Class I, II, IIIA and IIIB Liquids shall be allowed to be located adjacent to Level 2 and 3 aerosol products when the following conditions are met: 1. Class I, II, IIIA and IIIB liquid containers: Containers for Class I, II, IIIA and IIIB liquids shall be limited to 1.06-gallon (4-L) metal-relieving and nonrelieving style containers and 5.3-gallon (20-L) metal-relieving style containers.
2.Fire protection for Class I, II, IIIA and IIIB liquids: Automatic sprinkler protection for Class I, II, IIIA and IIIB liquids shall be in accordance with FC Chapter 57.