5105.1 General.
FC § 5105.1
The outdoor storage of Level 2 and 3 aerosol products, including storage in temporary storage trailers, shall be separated from exposures in accordance with FC Table 5105.1. FC Table 5105.1Distance to Exposures for Outdoor Storage of Level 2 and 3 Aerosol Products ExposureMinimum Distance from Aerosol Storage (feet) aPublic streets or private roads20Buildings50Exit discharge to a public street or private road50Lot lines20Other outdoor hazardous material storage50 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. The minimum separation distance indicated is not required where exterior walls having a 2-hour fire-resistance rating without penetrations separate the storage from the exposure. The walls shall extend not less than 30 inches above and to the sides of Level 2 and 3 aerosol products.