5005.2.2.5 Secondary containment for hazardous material liquids.
FC § 5005.2.2.5
Where required by FC Table 5005.2.1.4, buildings, rooms or areas where hazardous material liquids are used in vessels or systems shall be provided with secondary containment in accordance with FC 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following quantities: 1. Individual vessel or system: greater than 55 gallons (208 L).
2.Multiple vessels or systems: greater than 1,000 gallons (3785 L).