5005.1.10 Liquid transfer.
FC § 5005.1.10
Liquids having a hazard ranking of 3 or 4 pursuant to NFPA 704 shall be transferred by one of the following methods: 1. From safety cans complying with the requirements of UL 30.
2.Through an approved closed piping system.
3.From containers or tanks by an approved pump taking suction through an opening in the top of the container or tank.
4.From containers or tanks by gravity through an approved self-closing or automatic-closing valve when the container or tank and dispensing operations are provided with spill control and secondary containment in accordance with FC 5004.2. Highly toxic liquids shall not be dispensed by gravity from tanks.
5.Approved engineered liquid transfer systems. Exceptions: 1. Liquids having a hazard ranking of 4 when dispensed from approved containers not exceeding 1.3 gallons (5 L).