What is NYC FC § 3706.6.2?

Quick Answer

This section outlines the fire protection requirements for the substructure of waterfront structures. It specifies methods such as fire stops, sprinkler systems, water spray nozzles, and trench systems to ensure adequate fire safety. Applies to waterfront structure owners and operators responsible for fire protection measures.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

3706.6.2 Substructure.

FC § 3706.6.2

The substructure of the waterfront structure shall be protected by one of the following methods: 1. Fire stops at intervals of 150 feet (45 720 mm); and 1.1. A sprinkler system arranged for discharge of water to the entire substructure area; or 1.2. Protected openings through decking for revolving nozzles or other water discharge equipment, so arranged as to permit water discharge onto the entire substructure area. Such openings shall be a minimum of 6 1/2 inches (165 mm) in diameter and spaced at 25 feet (7620 mm) intervals longitudinally and transversely. No cargo shall be stored on deck openings adjacent to the substructure fire stops and those in the main and fire hose aisles.

2.A system of water spray nozzles arranged to permit water discharge onto the entire substructure area and installed in accordance with the Building Code.

3.A system of trenches across the waterfront structure every 100 feet (30 480 mm). Such trenches shall not exceed 12 inches (305 mm) in width, shall be of substantial construction that conforms to the rest of the waterfront structure, shall extend to within 5 feet (1524 mm) of the sides of the waterfront structure, and shall have openings protected in sections not to exceed 25 feet (7620 mm) for access or removal in the event of fire. No cargo shall be placed directly above these openings, and durable signs shall be conspicuously posted on the waterfront structure to indicate the location of these openings.

4.A system of deck openings and under-deck sprinkler protection approved by the commissioner. Openings shall be spaced at 25 feet (7620 mm) intervals longitudinally and transversely. No cargo shall be placed directly above these openings, and durable signs shall be conspicuously posted on the waterfront structure to indicate the location of these openings.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 3706.6.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters