This section outlines the construction requirements for manifolds and vaporizers used in oxygen service, specifying that they must withstand pressures of 250 psig and have a minimum bursting pressure of 1,000 psig. It also mandates the inclusion of safety relief devices to operate below 500 psig. Applies to building owners utilizing oxygen systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

3306.2.1.4 Manifolds and vaporizers.

FC § 3306.2.1.4

Manifolds and vaporizers shall be constructed of materials suitable for oxygen service at a pressure of 250 psig (1724 kPa). Such manifolds and vaporizers shall have a minimum bursting pressure of 1,000 psig (6895 kPa) and shall be protected with safety relief devices which will relieve at or below 500 psig (3448 kPa).