3209.3 Carousel storage.
FC § 3209.3
High-piled storage areas having greater than 500 square feet (46 m 2) of carousel storage shall be provided with automatic shutdown in accordance with one of the following: 1. An automatic smoke detection system installed in accordance with the construction codes, including the Building Code, with coverage extending 15 feet (4572 mm) in all directions beyond unenclosed carousel storage systems and which sounds a local alarm at the operator's station and stops the carousel storage system upon the activation of a single detector.
2.An automatic smoke detection system installed in accordance with the construction codes, including the Building Code and within enclosed carousel storage systems, that sounds a local alarm at the operator's station and stops the carousel storage system upon the activation of a single detector.