This section outlines the fire protection requirements for shelf storage in buildings. Shelf storage exceeding 12 feet but less than 15 feet must comply with NFPA 13 requirements, while storage at 15 feet or more requires special fire protection measures, such as in-rack sprinklers. Applies to building owners managing storage facilities.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

3207.2.1 Shelf storage.

FC § 3207.2.1

Shelf storage greater than 12 feet (3658 mm) but less than 15 feet (4572 mm) in height shall be in accordance with the fire protection requirements set forth in NFPA 13, as modified by FC Appendix B. Shelf storage 15 feet (4572 mm) or more in height shall be protected in an approved manner with special fire protection, such as in-rack sprinklers.