What is NYC FC § 3206.2?

Quick Answer

This section outlines the extent and type of fire protection required for high-piled storage areas, specifying that fire detection systems and other features must extend beyond the storage area or to a permanent partition. It applies to building owners managing facilities with high-piled storage configurations.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

3206.2 Extent and type of protection.

FC § 3206.2

Where required by FC Table 3206.2, fire detection systems, smoke and heat removal, draft curtains and sprinkler design densities shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. Where portions of high-piled storage areas have different fire protection requirements because of commodity, method of storage or storage height, the fire protection features required by FC Table 3206.2 within this area shall be based on the most restrictive design requirements.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 3206.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters