2308.8.1.2.3 Separation.
FC § 2308.8.1.2.3
The structure or appurtenance used for stabilizing the container shall be separated from other equipment or features as set forth in FC Table 2308.8.1.2.3. FC Table 2308.8.1.2.3Separation Distance for Atmospheric Venting of CNG Equipment or FeatureMinimum Separation(feet)Equipment or FeatureMinimum Separation(feet)Buildings25Building openings25Lot lines15Public street or private roads15Vehicles25CNG compressor and storage containers25CNG dispensers25 For SI: 1 foot = 304.8 mm.