This section outlines the requirements for initial piping tests for primary and secondary containment piping, specifying hydrostatic and pneumatic testing pressures and durations. The statute ensures that all piping systems are leak-free before backfill and installation. Applies to building owners involved in the installation of piping systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

2306.9.2 Initial piping test.

FC § 2306.9.2

Prior to backfill, primary piping shall be tested hydrostatically to one and one-half times the maximum anticipated operating pressure, but not less than 15 pounds per square inch (psig) (103.4 kPa). After backfill and installation of the top slab, discharge piping shall be tested hydrostatically at one and one-half times the maximum anticipated pressure, but not less than 50 pounds per square inch (psig) (345 kPa). Secondary containment piping (annular space) shall be tested pneumatically at 5 pounds per square inch (psig) (34.5 kPa) utilizing an inert gas; however, air may be used if the tank system or piping system does not contain any liquid motor fuel or combustible vapor. Hydrostatic test pressure shall be maintained for sufficient time to complete visual inspection but not less than 1 hour. The test shall show that there is no evidence of leakage. Test pressure for aboveground tank piping shall be at one and one-half times the maximum anticipated operating pressure but not less than 100 pounds per square inch (psig) (690 kPa).

Common Questions

Our team

Meet the people you will work with

TI

Tiffany Irizarry

Legal Coordinator

OATH / DOB
TI

Tiffany Irizarry

Legal Coordinator

OATH / DOB

Free case review

Have a matter that touches § 2306.9.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

reception@nacmiaslaw.com

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters