2306.2.4 Location requirements for aboveground tanks at fleet motor fuel-dispensing facilities.
FC § 2306.2.4
Tanks shall be located in accordance with FC Table 2306.2.4 and as follows: 1. A minimum of 25 feet (7620 mm) from a subway grating, entrance or exit.
2.At a location that will not obstruct or interfere with any means of egress or department access.
3.Tanks shall not be installed under electrical transmission lines, bridges, or public highways. FC Table 2306.2.4Minimum Separation Requirements for Aboveground Tanks at Fleet Motor Fuel-Dispensing Facilities Class of Liquid and Tank TypeIndividual Tank Capacity(gallons)Minimum Distance from Nearest Building(feet) Minimum Distance from Lot Line(feet)Minimum Distance from Public Street or Private Road(feet)Minimum Distance Between Tanks(feet)Liquid motor fuel tanks4000Greater than 400015251525151533 For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L.