2306.2.3.2 Tank capacity.
FC § 2306.2.3.2
The capacity of each tank shall not exceed 10,000 gallons (37 850 L). Not more than a total of 10,000 gallons (37 850 L) of liquid motor fuel shall be stored aboveground at any facility. The total storage capacity at a facility in both aboveground and underground tanks shall not exceed 40,000 gallons (15 140 L) of liquid motor fuel. Each tank shall have a separate fill line and a separate vent line that are separate from the fill and vent lines of other tanks. Exception: When approved, individual tanks may exceed 10,000 gallons (37 850 L) but shall not exceed 12,000 gallons (45 420 L).