105.6 Required permits.
FC § 105.6
The commissioner shall issue the following permits for the manufacture, storage, handling, use, transportation and sale of the following materials, the conduct of the following operations, and the design, installation, operation and maintenance of the following facilities in accordance with this code and the construction codes, including the Building Code: Aerosol products. A permit is required to store, handle or use an aggregate quantity of Level 1, 2 or 3 aerosol products in excess of 100 pounds (45.4 kg) net weight. Alcohol-based hand rubs. The storage, handling and use of alcohol-based hand rubs is subject to the following permit requirements: 1. A permit is required to store, handle or use flammable or combustible alcohol-based hand rubs on a premises, for use on the premises, in quantities exceeding 275 gallons (1041 L), when stored, handled or used in a portable container designed for consumer use, with a capacity not exceeding 68 fluid ounces (2.01 L), that does not require handling of the contents, including disposable wall-mounted and table-top dispensers and wall-mounted dispensers using sealed refills.
2.A flammable liquids permit or combustible liquids permit, as applicable, is required to store, handle or use flammable or combustible alcohol-based hand rubs in any tank, intermediate bulk container or stationary installation; portable container with a capacity exceeding 68 fluid ounces (2.01 L); or portable container of any size that requires handling of the contents prior to use for hand sanitizing purposes, including any pouring, pumping or other transfer of the contents to a dispenser. Amusement buildings. A permit is required to establish and operate a special amusement building. Asphalt melter. A permit is required to store, handle or use an asphalt melter. Automotive salvage and wrecking facilities. A permit is required to establish and operate an automotive salvage and wrecking facility. Auxiliary radio communication (ARC) systems. A permit is required to establish and operate a fire department in-building auxiliary radio communication system. Aviation operations. A permit is required for the following aviation operations: 1. To operate or maintain an aircraft-fueling vehicle.
3.To conduct a helicopter landing at other than an approved heliport, helistop or airport.
4.To conduct a helicopter lift operation.
5.To conduct a hot air balloon operation. Cellulose nitrate film. A permit is required to store, handle or use cellulose nitrate film in the following quantities: 1. Any quantity in a Group A occupancy.
6.to operate a bulk plant or terminal or bulk transfer facility where flammable and combustible liquids are blended, produced, processed, transported, stored, dispensed or used.
7.to manufacture flammable or combustible liquids.
8.to store and/or use fuel oil stored on a barge, marine vessel or watercraft moored to or anchored at privately owned waterfront property.
9.to store and use fuel oil in quantities exceeding 10 gallons (38 L) on mobile heating and power generating trailers.
10.to store and use gasoline in quantities exceeding 2 1/2 gallons (9.5 L) in a single item of portable fueled equipment lawfully stored in accordance with FC 313 or an aggregate of 10 gallons (38 L) in all such portable fueled equipment stored at a premises. Fleet Fueling. The transfer of Class II and III liquids directly from a cargo tank through approved dispensing equipment into the fuel tank of a motor vehicle at an approved off-street location where fleet vehicles are parked. Floor finishing. A permit is required to conduct floor finishing or surfacing operations over an area exceeding 350 square feet (33 m2) using Class I or Class II liquids. Fruit and crop ripening. A permit is required to establish and operate a fruit-, or crop-ripening facility or conduct a fruit-ripening process using ethylene gas. Fumigation and insecticidal fogging. A permit is required to establish and operate a facility in which a fumigant or insecticidal fogger is used in a stationary installation. Hazardous materials. A permit is required to store, handle or use hazardous materials in quantities exceeding those set forth in FC Table 105.6(3). FC Table 105.6(3)Permit Quantities for Hazardous Materials Type of MaterialQuantityType of MaterialQuantityCombustible liquidsSee FC 105.6 for flammable and combustible liquids Corrosive materials Gases Liquids SolidsSee FC Table 105.6(1)55 gallons1,000 pounds Explosive materials See FC 105.6 for explosive materials Flammable materials Gases Liquids SolidsSee FC Table 105.6(1)See FC 105.6 for flammable and combustible liquidsSee FC Table 105.6(4) Highly toxic materials Gases Liquids SolidsSee FC Table 105.6(1)Any quantityAny quantity Oxidizing materials Gases Liquids Class 4 Class 3 Class 2 Class 1 Solids Class 4 Class 3 Class 2 Class 1See FC Table 105.6(1)Any quantity1 gallon10 gallons55 gallonsAny quantity10 pounds100 pounds500 pounds Organic peroxides Liquids Class I Class II Class III Class IV Class V Solids Class I Class II Class III Class IV Class VAny quantityAny quantity1 gallon2 gallonsNo Permit RequiredAny quantityAny quantity10 pounds20 poundsNo Permit Required Pyrophoric materials Gases Liquids SolidsSee FC Table 105.6(1)Any quantityAny quantity Toxic materials Gases Liquids SolidsSee FC Table 105.6(1)10 gallons100 pounds Unstable (reactive) materials Gases Liquids Class 4 Class 3 Class 2 Class 1 Solids Class 4 Class 3 Class 2 Class 1See FC Table 105.6(1)Any quantityAny quantity5 gallons10 gallonsAny quantityAny quantity50 pounds100 pounds Water-reactive Materials Gases Liquids Class 3 Class 2 Class 1 Solids Class 3 Class 2 Class 1See FC Table 105.6(1)Any quantity5 gallons55 gallonsAny quantity50 pounds500 pounds For SI: 1 gallon = 3.785 L, 1 pound = 0.454 kg. FC Table 105.6(4)Permit Quantities for Flammable Solids Forms of Flammable SolidIndoors(pounds)Outdoors(pounds)Pigs, ingots, billets, heavy castings1001,000Light castings, light metallic products100125Scraps, shavings, powders, dusts1100Other flammable solids1100 For SI: 1 pound = 0.454 kg. Hazardous production material (HPM) facilities. A permit is required to store, handle or use hazardous production materials. High-piled storage. A permit is required to use an area exceeding 500 square feet (46 m2) in a building or structure or part thereof as a high-piled storage area. Hot work operations. A permit is required to conduct hot work, including the following types of hot work: 1. use of a flammable gas with oxygen.