421.5.1 System activation.
BC § 421.5.1
Activation of a gas detection alarm shall initiate the following notification and action: 1. Initiation of distinct audible and visible alarm signals both inside and outside of the hydrogen fuel gas room.
2.Automatic activation of the mechanical exhaust ventilation system.