415.11.10.1 Required electrical systems.
BC § 415.11.10.1
Emergency power shall be provided for electrically operated equipment and connected control circuits for the following systems: 1. HPM exhaust ventilation systems.
2.HPM gas cabinet ventilation systems.
3.HPM exhausted enclosure ventilation systems.
4.HPM gas room ventilation systems.
5.HPM gas detection systems.
6.Emergency alarm systems.
7.Manual and automatic fire alarm systems.
8.Automatic sprinkler system monitoring and alarm systems.
9.Automatic alarm and detection systems for pyrophoric liquids and Class 3 water-reactive liquids required in the New York City Fire Code.
10.Flow alarm switches for pyrophoric liquids and Class 3 water-reactive liquids cabinet exhaust ventilation systems required in the New York City Fire Code.
11.Electrically operated systems required elsewhere in this code applicable to the use, storage or handling of HPM.