407.4.3 Projections in nursing home corridors.
BC § 407.4.3
In nursing homes of Group I-2 occupancies, where the corridor width is a minimum of 96 inches (2440 mm), projections shall be permitted for furniture where all of the following criteria are met: 1. The furniture is attached to the floor or to the wall.
2.The furniture does not reduce the clear width of the corridor to less than 72 inches (1830 mm) except where other encroachments are permitted in accordance with Section 1005.7.
3.The furniture is positioned on only one side of the corridor.
4.Each arrangement of furniture is 50 square feet (4.6 m 2 ) maximum in area.
5.Furniture arrangements are separated by 10 feet (3048 mm) minimum.
6.Placement of furniture is considered as part of the fire and emergency preparedness plans in accordance with Section 1001.4.