2702.4 Required loads for optional standby power systems.
BC § 2702.4
In addition to any other loads, optional standby power systems shall be capable of providing power to the following standby and emergency power loads upon failure of the normal power supply: 1. Emergency lighting; 2. Fire alarm systems; and 3. Elevators as follows: 3.1. For Groups R-2 occupancies in buildings greater than 125 feet (38 100 mm) in height, at least one elevator serving all floors, or one elevator per bank where different banks serve different portions of the building; or 3.2. For all other buildings having occupied floors located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access, at least one elevator that serves all floors. Exception: Backup power systems that provide backup power for non-accessory public telecommunications equipment, such as rooftop telecommunications antennas, cooling equipment, routers, etc., need not provide power to the standby and emergency power loads listed in this section.













