2609.4 Area limitations.
BC § 2609.4
Roof panels shall be limited in area and the aggregate area of panels shall be limited by a percentage of the floor area of the room or space sheltered in accordance with Table 2609.4. Exceptions: 1. The area limitations of Table 2609.4 shall be permitted to be increased by 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
2.Low-hazard occupancy buildings, such as swimming pool shelters, shall be exempt from the area limitations of Table 2609.4, provided that the buildings do not exceed 5,000 square feet (465 m 2 ) in area and have a minimum fire separation distance of 10 feet (3048 mm).
3.Greenhouses that are occupied for growing plants on a production or research basis, without public access, shall be exempt from the area limitations of Table 2609.4 provided they have a minimum fire separation distance of 4 feet (1220 mm).
4.Roof coverings over terraces and patios in Group R-3 occupancies shall be exempt from the area limitations of Table 2609.4. Table 2609.4Area Limitations for Light-Transmitting Plastic Roof Panels Class of PlasticMaximum Area of Individual Roof Panels (square feet)Maximum Aggregate Area of Roof Panels (percent of floor area)CC1 300 30 CC2 100 25 For SI: 1 square foot = 0.0929 m 2 .