2406.2 Impact test.
BC § 2406.2
Where required by other sections of this code, glazing shall be tested in accordance with CPSC 16 CFR Part 1201. Glazing shall comply with the test criteria for Category II, unless otherwise indicated in Table 2406.2(1). Table 2406.2(1) Minimum Category Classification of Glazing Using CPSC 16 CFR 1201 Exposed Surface Area of One Side of One Lite Glazing in Storm or Combination Doors(Category class) Glazing in Doors (Category class) Glazed Panels Regulated by Section 2406.4.3 (Category class) Glazed Panels Regulated by Section 2406.4.2 (Category class) Doors and Enclosures Regulated by Section 2406.4.5 (Category class) Sliding Glass Doors Patio Type (Category class) 9 square feetor lessI I No requirement I II II More than 9 square feetII II II II II II For SI: 1 square foot = 0.0929 m 2 . Exception: Glazing not in doors or enclosures for hot tubs, whirlpools, saunas, steam rooms, bathtubs and showers shall be permitted to be tested in accordance with ANSI Z97.
1.Glazing shall comply with the test criteria for Class A, unless otherwise indicated in Table 2406.2(2). Table 2406.2(2)Minimum Category Classification of Glazing Using ANSI Z97.1 Exposed Surface Area of One Side of One Lite Glazed Panels Regulated by Section 2406.4.3 (Category class) Glazed Panels Regulated by Section 2406.4.2 (Category class) Doors and Enclosures Regulated by Section 2406.4.5 a (Category class) 9 square feetor lessNo requirement B A More than 9 square feetA A A For SI: 1 square foot = 0.0929 m 2 . a. Use is only permitted by the exception to Section 2406.2. (Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023) Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.