What is NYC BC § 2113.11.2.2?

Quick Answer

This section specifies the requirements for lining masonry chimneys with approved refractory brick and mortar. The lining must start at least 2 feet below the lowest chimney connector entrance and extend to the top for chimneys terminating 25 feet or less above the connector. Applies to building owners responsible for chimney construction and maintenance.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

2113.11.2.2 Lining.

BC § 2113.11.2.2

Masonry chimneys shall be lined with an approved medium-duty refractory brick not less than 4 1/2 inches (114 mm) thick laid on the 4 1/2-inch bed (114 mm) in an approved medium-duty refractory mortar. The lining shall start 2 feet (610 mm) or more below the lowest chimney connector entrance. Chimneys terminating 25 feet (7620 mm) or less above a chimney connector entrance shall be lined to the top.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 2113.11.2.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters