What is NYC BC § 1817.4.1?

Quick Answer

This section outlines the requirements for underpinning when foundation loads are transferred to a lower bearing level. It specifies that underpinning must consist of engineered systems such as concrete piers or drilled piles, and details the calculation of bearing pressure at the base of the underpinning. Applies to building owners involved in foundation work.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1817.4.1 Underpinning.

BC § 1817.4.1

If the foundation loads are to be transferred to a lower bearing level, underpinning consisting of concrete piers, drilled piles, jacked piles, bracket piles, or similar engineered systems to transfer the existing building loads below the bottom of the proposed excavation shall be installed. The bearing pressure at the base of the underpinning shall be computed accounting for all vertical loads and any overturning moments present due to lateral earth and water pressures, and shall be less than or equal to the allowable bearing pressure of the bearing stratum.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1817.4.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters