1705.5.3.1 Erection.
BC § 1705.5.3.1
The erection of prefabricated wood I-joists and/or glued prefabricated parallel chord wood trusses shall be subject to special inspection for compliance with the approved construction documents, the requirements of Sections 1704.1, and the following: 1. All installed materials shall be clean, straight and otherwise undamaged. Members and parts shall not be stretched, bent, or otherwise distorted unless such forming is in the integral part of the design. The special inspector shall ensure that damaged members are not used for construction.
2.Profiles of members used structurally shall conform to the dimensions specified in the approved construction documents. The installation shall be inspected for compliance with the approved construction documents regarding locations, positions, beam separators, bearing surfaces, fasteners, screws, bolts and bracing, as applicable.
3.The size, location, and number of penetrations shall be inspected for compliance with the approved construction documents and manufacturers' instructions.
4.Temporary bracing, shoring, jacks, etc., shall not be removed until the special inspector determines that they are no longer needed. (Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023) Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.