What is NYC BC § 1705.14.4.2?

Quick Answer

This section specifies the requirements for determining the thickness of sprayed fire-resistant material applied to floor, roof, and wall assemblies, in accordance with ASTM E 605. It mandates that a minimum of four measurements be taken for each 1,000 square feet of the sprayed area on each story. Applies to building owners involved in construction or renovation.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1705.14.4.2 Floor, roof and wall assemblies.

BC § 1705.14.4.2

The thickness of the sprayed fire-resistant material applied to floor, roof and wall assemblies shall be determined in accordance with ASTM E 605, making not fewer than four measurements for each 1,000 square feet (92.9 m 2 ) of the sprayed area in each story or portion thereof.