This section outlines the required contents of structural peer review reports, including compliance with previous items, documentation of design criteria, and statements from peer reviewers regarding code compliance. The statute is enforced by the Department of Buildings (DOB). Applies to building owners involved in structural design and peer review processes.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1618.7.2 Contents.

BC § 1618.7.2

The report shall demonstrate, at a minimum, compliance with Items 1 through 12 of Section 1618.6.1. In addition, the report shall also include the following: 1. A list of construction documents, including the latest revision dates submitted to the department for approval, as well as geotechnical reports, wind tunnel studies and other reports utilized in the design.

2.The codes and standards used in the structural design of the project.

3.The structural design criteria, including loads and performance requirements.

4.The basis for design criteria that are not specified directly in applicable codes and standards. This should include reports by specialty consultants such as wind tunnel study reports and geotechnical reports. Generally, the report should confirm that existing conditions at the site have been investigated as appropriate and that the design of the proposed structure is in general conformance with these conditions.

5.The basis of performance-based design and its appropriateness of use.

6.A statement that the qualification and independence of the peer reviewer is in accordance with Section 1618.5.

7.Peer review reports shall provide an unconditional statement that must be either an acceptance or rejection of code compliance of the structural design required to be reviewed by this section.

8.The structural peer review reports shall contain a statement that geotechnical peer review reports and/or wind tunnel peer review reports, when required, have been received with an unconditional statement of acceptance by the authors of those reports.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1618.7.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters