1607.11.1 Basic uniform live load reduction.
BC § 1607.11.1
Subject to the limitations of Sections 1607.11.1.1 through 1607.11.1.4 and Table 1607.1, members for which a value of KLLAT is 400 square feet (37.16 m 2 ) or more are permitted to be designed for a reduced uniformly distributed live load, L, in accordance with the following equation: (Equation 16-30) where: where: L = Reduced design live load per square foot (m2) of area supported by the member. Lo = Unreduced design live load per square foot (m2) of area supported by the member (see Table 1607.1). KLL = Live load element factor (see Table 1607.11.1). AT = Tributary area, in square feet (m 2 ). L shall not be less than 0.50Lo for members supporting one floor and L shall not be less than 0.40Lo for members supporting two or more floors. Table 1607.11.1Live Load Element Factor KLL Element KLLInterior columnsExterior columns without cantilever slabs44Edge columns with cantilever slabs3Corner columns with cantilever slabsEdge beams without cantilever slabsInterior beams222All other members not identified above including: Edge beams with cantilever slabs Cantilever beams One-way slabs Two-way slabs Members without provisions for continuous shear transfer normal to their span1