What is NYC BC § 1028.4.2?

Quick Answer

This section outlines the fire-resistance requirements for egress court walls in buildings with egress courts less than 10 feet wide. The walls must have a minimum 1-hour fire-resistance rating, and openings must be protected with a minimum 3/4 hour fire protection rating. Applies to building owners with specific egress court configurations.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1028.4.2 Construction and openings.

BC § 1028.4.2

Where an egress court serving a building or portion thereof is less than 10 feet (3048 mm) in width, the egress court walls shall have not less than 1-hour fire-resistance-rated construction for a distance of 10 feet (3048 mm) above the floor of the egress court. Openings within such walls shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour. Exception: Protection of exterior walls shall not be required where: 1. Egress courts serving an occupant load of less than 10.

2.Egress courts serving Group R-3.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1028.4.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters