1023.11.1 Termination and extension.
BC § 1023.11.1
A smokeproof enclosure or pressurization alternative shall terminate at an exit discharge or a public way. The smokeproof enclosure or pressurization alternative shall be permitted to be extended by an exit passageway in accordance with Section 1023.3. The exit passageway shall be without openings other than the fire door assembly required by Section 1023.3.1 and those necessary for egress from the exit passageway. The exit passageway shall be separated from the remainder of the building by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Exceptions: 1. Openings in the exit passageway serving a smokeproof enclosure are permitted where the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure, and openings are protected as required for access from other floors.
2.Openings in the exit passageway serving a pressurization alternative are permitted where the exit passageway is protected and pressurized in the same manner as the pressurization alternative.
3.The fire barrier separating the smokeproof enclosure or pressurization alternative from the exit passageway is not required, provided the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure or pressurization alternative.
4.A smokeproof enclosure or pressurization alternative shall be permitted to egress through areas on the level of exit discharge or vestibules as permitted by Section 1028.