What is NYC BC § 1023.11.1?

Quick Answer

This section outlines the requirements for the termination and extension of smokeproof enclosures or pressurization alternatives at exit discharges or public ways. It specifies conditions for exit passageways, including separation by fire barriers and exceptions for openings. Applies to building owners responsible for fire safety compliance.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1023.11.1 Termination and extension.

BC § 1023.11.1

A smokeproof enclosure or pressurization alternative shall terminate at an exit discharge or a public way. The smokeproof enclosure or pressurization alternative shall be permitted to be extended by an exit passageway in accordance with Section 1023.3. The exit passageway shall be without openings other than the fire door assembly required by Section 1023.3.1 and those necessary for egress from the exit passageway. The exit passageway shall be separated from the remainder of the building by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Exceptions: 1. Openings in the exit passageway serving a smokeproof enclosure are permitted where the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure, and openings are protected as required for access from other floors.

2.Openings in the exit passageway serving a pressurization alternative are permitted where the exit passageway is protected and pressurized in the same manner as the pressurization alternative.

3.The fire barrier separating the smokeproof enclosure or pressurization alternative from the exit passageway is not required, provided the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure or pressurization alternative.

4.A smokeproof enclosure or pressurization alternative shall be permitted to egress through areas on the level of exit discharge or vestibules as permitted by Section 1028.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1023.11.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters