What is NYC BC § 1020.1.1?

Quick Answer

This section establishes fire-resistance rating requirements for interior corridors in various occupancy groups, detailing exceptions for specific conditions such as Group E, Group R, open parking garages, and certain Group B spaces. Applies to building owners managing properties with interior corridors.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1020.1.1 Interior corridors.

BC § 1020.1.1

Interior corridors shall be fire-resistance rated in accordance with Table 1020.1.1. Exceptions: 1. A fire-resistance rating is not required for corridors in an occupancy in Group E where each room that is used for instruction has not less than one door opening directly to the exterior and rooms for assembly purposes have not less than one-half of the required means of egress doors opening directly to the exterior. Exterior doors specified in this exception are required to be at ground level and open to a public way.

2.A fire-resistance rating is not required for corridors contained within a dwelling unit or sleeping unit in an occupancy in Group R.

3.A fire-resistance rating is not required for corridors in open parking garages.

4.A fire-resistance rating is not required for corridors in an occupancy in Group B that is a space requiring only a single means of egress complying with Section 1006.2.

5.Corridors adjacent to the exterior walls of buildings shall be permitted to have unprotected openings on unrated exterior walls where unrated walls are permitted by Table 602 and unprotected openings are permitted by Table 705.8. Table 1020.1.1Interior Corridor Fire-Resistance Rating Occupancy Occupant Load Served by Interior CorridorRequired Fire Resistance Rating (hours)Without sprinkler system With sprinkler system cOccupancy Occupant Load Served by Interior CorridorRequired Fire Resistance Rating (hours)Without sprinkler system With sprinkler system cH-1, H-2, H-3All Not Permitted 1 H-4, H-5Greater than 30 Not Permitted 1 A, B, E, F, M,S, UGreater than 30 1 0 RGreater than 30 1 d 0 I-2 a , I-4All Not Permitted 0 I-1, I-3All Not Permitted 1 b a. For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3. b. For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8. c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed. d. Interior corridors within dwelling or sleeping units in Group R occupancies pursuant to Section 1020.1.1, Exception 2 shall not require fire-resistance rating.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1020.1.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters