What is NYC BC § 1010.1.9.8?

Quick Answer

This section outlines the criteria for the installation and operation of sensor-released electrically locked egress doors in specific occupancy groups. It mandates features such as automatic unlocking during power loss, manual unlocking access, and integration with fire alarm and sprinkler systems. Applies to building owners of Group A, B, E, M, R-1, or R-2 occupancies.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1010.1.9.8 Sensor release of electrically locked egress doors.

BC § 1010.1.9.8

The electric locks on sensor released doors located in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Group A, B, E, M, R-1 or R-2 are permitted where installed and operated in accordance with all of the following criteria: 1. The sensor shall be installed on the egress side, arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor.

2.Loss of power to the lock or locking system shall automatically unlock the doors.

3.The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1220 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads "PUSH TO EXIT." When operated, the manual unlocking device shall result in direct interruption of power to the lock-independent of other electronics-and the doors shall remain unlocked for not less than 30 seconds.

4.Activation of the building fire alarm system, where provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset.

5.Activation of the building automatic sprinkler system or fire detection system, where provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset.

6.The door locking system units shall be listed in accordance with UL 294.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1010.1.9.8?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters