What is NYC BC § 1010.1.10.1?

Quick Answer

This section mandates that exit or exit access doors serving transformer vaults, battery storage rooms, or modular data centers be equipped with panic hardware or fire exit hardware. Additionally, it specifies requirements for doors near high-capacity electrical equipment. Applies to building owners with such facilities.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1010.1.10.1 Rooms with electrical equipment.

BC § 1010.1.10.1

Exit or exit access doors serving transformer vaults, rooms designated for batteries or energy storage systems, or modular data centers shall be equipped with panic hardware or fire exit hardware. Where rooms contain electrical rooms with equipment rated 800 amperes or more that contain overcurrent devices, switching devices or control devices and where the exit or exit access door is less than 25 feet (7629 mm) from the equipment working space, shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1010.1.10.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters