1009.8 Two-way communication.
BC § 1009.8
A two-way communication system complying with Sections 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator or bank of elevators on each accessible floor that is one or more stories above or below the level of exit discharge. Exceptions: 1. Two-way communication systems are not required at the landing serving each elevator or bank of elevators where the two-way communication system is provided within areas of rescue assistance in accordance with Section 1009.6.5.
2.Two-way communication systems are not required on floors provided with ramps conforming to the provisions of Section 1012.
3.Two-way communication systems are not required at the landings serving only service elevators that are not designated as part of the accessible means of egress or serve as part of the required accessible route into a facility.
4.Two-way communication systems are not required at the landings serving only freight elevators that are not designated as part of the accessible means of egress or serve as part of the required accessible route into a facility.
5.Two-way communication systems are not required at the landing serving a private residence elevator.