What is NYC BC § 1006.2.2.1?

Quick Answer

This section mandates the requirement of two exit access doorways in boiler, incinerator, and furnace rooms exceeding 500 square feet and with fuel-fired equipment over 400,000 Btu input capacity. The doorways must be spaced apart by a specified horizontal distance. Applies to building owners operating such facilities.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1006.2.2.1 Boiler, incinerator and furnace rooms.

BC § 1006.2.2.1

Two exit access doorways are required in boiler, incinerator and furnace rooms where the area is over 500 square feet (46.5 m 2 ) and any fuel-fired equipment exceeds 400,000 British thermal units (Btu) (422 000 KJ) input capacity. Where two exit access doorways are required, one such doorway is permitted to be served by a fixed ladder or an alternating tread device. Exit access doorways shall be separated by a horizontal distance equal to one-half the length of the maximum overall diagonal dimension of the room.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1006.2.2.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters